PPL IMP 1094 A
USER GUIDE
GB
CONFIGURATION SWITCH
1 2 3 4
Sensor mode 3&4 :
- Regulation on internal room
- Regulation on external probe
- Regulation internal room sensor
with lower limit floor on ext. probe
- Regulation on internal room sensor
with upper limit floor on ext. probe
static differential of
or proportional on
Regulation mode 2:
NC Actuator of
NO Actuator on
Actuator type 1:
on
off
Dual Sensing public area Thermostat 230
ac ANO WFHT 032 (20321)
Dual Sensing public area Thermostat 230Vac ANC WFHT 033 (20322)
TECHNICAL CHARACTERISTICS
MODES DESCRIPTION
- This thermostat is specially made for public area (school, office ….)
- Electronic thermostat with night reduction mode for water floor heating
systems controlled by actuators.
- External pilot wire for night reduction, equipped with an internal switch to
select comfort, reduction or clock mode.
- Possibility to regulate either the floor or room temperature, or combined
(in this case, the floor sensor is used as temperature limiter)
- Silent (triac output), to be connected directly to actuators (see connecting
drawing on the installation sheet) or to our Modular connecting system.
In this case
lease refer to the connectin
box datasheet
LED INDICATOR
Red: Heating indication
Green: reduction mode by clock (pilot wire)
Orange: Heating during reduction mode by clock (pilot wire)
Red blinking: - 0.5 second cycle => Internal & external sensor failures
- 1 second cycle => Internal sensor failure
- 2 seconds cycle => External sensor failure
Floor limit
settin
.
Room
settin
.
Select
mode.
Configuration
switch.
LED Indicator.
Screw connector for
external sensor.
Screw connector for
Power supply,
output and
clock (pilot wire)
Measured temperature
precision
0.1°C (or 0.2°F)
Operating temperature
0°C - 50°C (or 32°F – 122°F)
Setting temperature range
5°C – 30°C (or 41°F - 86°F)
Floor limiting temperature
range
10°C – 40°C (or 50°F - 104°F)
Regulation
characteristics
Proportional band 10min for 2°K
or Static differential 0.5°K
Electrical Protection
Class II - IP30
Power Supply
230 VAC +/- 10%
Output
TRIAC output 230 VAC, 75 W max.
( 15 actuators)
External Floor sensor
NTC (10K Ohms) 3m
Soft Version
V 1.4x
Comentários a estes Manuais